FCD WCAIM2068-00 DeviceNet Interface for Series 75 Electric Valve Actuator 7
8 Electrical Requirements
Table 2 represents approximate current draw (at rated stall torque) in
amperes at various voltages for each motor.
Actual values depend on several variables. For exact values, test the
unit at a particular load.
Table 2: Approximate Current Draw (amps)
Suffix
Code
Duty
Cycle
Voltage
Actuator Size
10 12 15 20 22 23
Blank 20% 120 AC — — 0.7 — — —
Blank 25% 120 AC 0.7 0.7
— 1.5 1.5 —
2 10% 120 AC 1.5 1.5 — 2.9 2.9 —
4 75% 120 AC 0.3 0.3 — 0.7 0.7 0.7
5 100% 120 AC 0.25 0.25 — 0.5 — —
Blank 25% 240 AC 0.4 0.4
— 0.9 0.9 —
2 10% 240 AC 0.6 0.6 — 1.3 1.3 —
4 75% 240 AC 0.15 0.15 — 0.3 0.3 0.3
5 100% 240 AC — — — — — —
Table 3: Cycle Time (Sec.)
Actuator Size
Suffix
Code 10 12 15 20 22 23
Blank 5 8 5 5 8 —
2 2.5 4 — 2.5 4 —
4 17, 15 27, 25 — 17, 15 27, 25 25
5 17 27 — 27 — —
9 Illustrations
9.1 DeviceNet Board Assembly Installation
Table 4
Item Qty Description
1 1 DeviceNet Circuit Board
2 2 6-32 Socket Head Cap Screw (1.00")
3 2 Hex Spacers (.50")
4 1 4-40 Round Head Screw (1.50")
5 2 6 Lockwasher
6 2 6-32 Round Head Screw (.25")
7 3 4-40 Round Head Screws (.38")
8 1 Relay Board
9 1
Round Head Screw (1.00") – Reused from switch
mounting
Figure 3: DeviceNet Board Assembly