Flowserve ValveAnalysis Manuale Utente Pagina 13

  • Scaricare
  • Aggiungi ai miei manuali
  • Stampa
  • Pagina
    / 16
  • Indice
  • SEGNALIBRI
  • Valutato. / 5. Basato su recensioni clienti
Vedere la pagina 12
13
ValveAnalysis Diagnostic Software Module FCD
VLENIM0113-01 – 1/06
flowserve.com
HDR
This measurement plots and calculates the hysteresis, deadband, and repeatability. The graph shows the
Position Error vs. Command. The Y-axis is labeled “Position Error %” which is equal to the Command
minus Position in percent. The X-axis is labeled Command as a percent of full stroke. Flowserve
ValveAnalysis then calculates the average and maximum combined hysteresis plus deadband and
repeatability.
Linearity
The third tab shows a graph of the valve’s linearity using two methods: average error and least-square
line. Flowserve ValveAnalysis also calculates the Linearity Error as a +/- percent. The Linearity Error is
shown directly below the graph.
Vedere la pagina 12
1 2 ... 8 9 10 11 12 13 14 15 16

Commenti su questo manuale

Nessun commento