Wiring
Wiring diagram
Use screened three-core cable, min. conductor size 0.5 mm², max. length 500 m.
1. Lift up the retaining clip and remove the upper part of the connector . Fig. 3
2. Remove screw and connector insert .
3. Completely unscrew the cable gland and slip it over the cable .
4. Strip off cable insulation coating and remove conductor end insulation.
5. Insert cable into the upper part of the connector and effect wiring to connector
insert acc. to wiring diagram. Fig. 4
6. Fix connector insert with the aid of screw , screw in cable gland and tighten.
7. Insert the upper connector part into the lower connector part and lock by
means of the retaining clip .
Fig. 4
H G
R
S
Q P
P
P G
S
S R Q
G I
H
U
M
C
M
321
4
5
6
Pt 1000
NRG 211
NRV 2-30
ϑ
2
1
6
3
4
6
5