MX/QX FOUNDATION Fieldbus Field Unit FCD LMENIM2330-01 – 08/11
16
Figure 2.6 – Fieldbus Power Supply with External Termination
Figure 2.7 – Fieldbus Power Supply with MX/QX FF Termination
2.6 Site and Network Cable Preparation
2.6.1 Site Preparation
Prepare the site and associated equipment for operation of the MX/QX FF controlled MX/QX actuators
as follows:
1. Prepare a detailed site plan consisting of the following:
Actuator locations and tag numbers
Junction boxes and terminal strip locations and tag numbers
Terminators and power supplies/conditioners, and repeaters
Provide free access to the MX/QX control panel and terminal block for setup, configuration,
and troubleshooting.
T
FOUNDATION
Fieldbus
Interface
+
-
Fieldbus
Power
Supply
Shielded Wire Pair
T
Field
Device
Field
Device
Field
Device
T
FOUNDATION
Fieldbus
Interface
+
-
Fieldbus
Power
Supply
Shielded Wire Pair
Field Device
Field
Device
Field
Device
T