Controller Menu – continued –
3-element continuous controller setup
1. Press button Continuous controller in the menu 3-element controller setup.
2. The name of the controller is highlighted in
yellow.
3. The green input fields Steam flowrate,
Water flowrate and Level show the ad-
justed signals. Click in the input field to
show all established signals.
4. Select the signal that indicates the re-
quired parameters. For more information
on the setup and configuration of the
equipment see menu CAN Input and An-
alog Input.
5. The green input field Rating shows the adjusted value. To change the value click in
the input field. The value rates the influence of the difference between steam and wa-
ter flowrate on the measured level signal.
6. The current value appears in the input mask. Use the on-screen keyboard to over-
write or modify the value.
7. To toggle between internal and external setpoint press button Internal setpoint/ Ex-
ternal setpoint.
8. To enter the signal for an external setpoint click in the green input field. All estab-
lished sensing elements will be indicated.
9. Select the signal that indicates the required parameters. For more information on the
setup and configuration of the equipment see menu CAN Input and Analog Input.
10. The green input field Manip. variable shows the manipulated variable element. To
select a signal for the manipulated variable click in the green input field. All adjusted
signals will be indicated.
11. Select the controller signal to which the manipulated variable shall be sent. You will
find more information on equipment setup in the menu Analog Output.
12. The green input field Position shows the position indicator. To select a position feed-
back signal click in the green input field. All adjusted signals will be indicated.
3-element continuous
controller setup
Logo
NC
Name
Steam flowrate
Water flowrate
Rating
Level
Int. setpoint
NC
NC
NC
NC
0.000