57
Controller Menu – continued –
3-element continuous controller setup - continued -
13. Select the signal that indicates the required parameters. For more information on the
setup and configuration of the equipment see menu CAN Input and Analog Input.
14. The green input field Offset shows the current value. To enter or change a value click
in the input field.
15. The adjusted value appears in the input mask. Use the on-screen keyboard to over-
write or modify the value.
16. The green input field MIN limit shows the current limit. To enter or change a value
click in the input field.
17. The adjusted value appears in the input mask. Use the on-screen keyboard to over-
write or modify the value.
18. The green input field MAX limit shows the current limit. To enter or change a value
click in the input field.
19. The adjusted value appears in the input mask. Use the on-screen keyboard to over-
write or modify the value.
Note
The MIN and MAX limit values specify the admissible manipulated variable
range of the controller.
Controlled actual value = Level - (steam flowrate - water flowrate) x rating
if steam flowrate – water flowrate > 0.
If the steam or water flowrate signal is faulty, the controller will only use the
actual value of the level.